Enhanced Entropy-Based Metric for Characterization of Delayed Voltage RecoveryEnsuring accurate violation detection in power systems is paramount for operational reliability. This paper introduces an enhanced voltage recovery violation index (EVRVI), a comprehensive index designed to quantify fault-induced delayed voltage recovery (FIDVR). EVRVI enhances traditional entropy-based methods by leveraging Empirical Mode Decomposition (EMD) to extract key features from the voltage signal, which are then used to quantify over-voltage (OV) and under-voltage (UV) events. Our simulations on the Nordic system, involving over 245k scenarios, demonstrate EVRVI's superior ability to identify and categorize voltage recovery issues compared to the traditional entropy-based measure. EVRVI not only significantly reduces false negatives in violation detection but also provides a reliable framework for over-voltage detection, making it an invaluable tool for modern power system studies.